Briton 996 manual

7.5 · 1
PDF manual
 · 13 páginas
Inglés
manualBriton 996

INSTALLATION INSTRUCTIONS

BRITON 996 FIG.1

ELECTRO MAGNETIC HOLD OPEN/FREE SWING DOOR CLOSER

24VDC

SURFACE FIXED TO ‘PULL’ (HINGE) SIDE OF DOOR.

SIZE 3 closer suitable for doors up to 950mm wide and 60kg in weight

SIZE 4 closer suitable for doors up to 1100mm wide and 80kg in weight

SIZE 5 closer suitable for doors up to 1250mm wide and 100kg in weight

This closer unit incorporates an electro magnet which is normally interfaced with a detector/alarm system.
In an emergency or a power failure, the electro magnet when de-energised will cause the closer to close the
door into its frame. A 13mm A/F spanner is required
to carry out adjustments to arm set or convert from hold
open to free swing function.
Hold open function enables unit to hold door open until automatically released or pulled closed manually.
Angle of hold can be adjusted from 85° to 95° approx. and 103° to 110° approx.
Free Swing function
setting allows door to be independent of closer control. When unit is automatically
released the door will be driven closed from whatever position it may have been left open. Adjustment of
catch plate provides for a free swing variance of 85° to 95° approx. Door can open to approx. 110° max.
subject to hinge projection and surrounding structure.
Warning: When Briton 996 is used in the free swing mode the door is not under the control of the damping
action and will slam in windy or draughty conditions.
THIS CLOSER UNIT IS EASILY CONVERTED TO SUIT EITHER HAND OF DOOR, for conversion
instructions see diagram 4.
IMPORTANT
Door must swing freely and close firm into its rebate to enable the closer to operate efficiently. This is
particularly important for fire/smoke doors and we recommend that doors be hung on ball bearing butt hinges
to BS EN 1935 and that latches and smoke seals be of a type that offer minimum resitance to closing.
Failure to address these requirements may result in an ineffective fire/smoke door installation.
DOOR STOP MUST BE FITTED TO PREVENT DOOR FROM OPENING JUST
BEYOND SET ANGLE OF
HOLD OPEN OR FREE SWING SETTING.
Under no circumstances should the door closer be dismantled.

ELECTRICAL INFORMATION

SPECIFICATION Electro-magnet continuous rating: 2.35 watts max at 26v DC.
Power Requirements: 24v DC - 90 mA nominal.
TESTING Check that voltage is within specified range at each unit after installation.
It is recommended that the equipment is tested at weekly intervals for correct function.
NOTE: Power for ancillary devices must not be drawn from the alarm system except under alarm
conditions and then must not reduce the reliability of the supply. (BS.5839 Pt. 1).
TYPICAL WIRING DIAGRAM
NOTE: Power supply feed to electro magnet is through flexible armoured loop.
IMPORTANT
This closer should be installed by a competent fixer who must pass these instructions onto the site or
maintenance manager once the closer unit has been satisfactorily fixed, wired and tested.
No Responsibility can be accepted by the manufacturers if these installation instructions are disregarded.
Diagram 1
24v DC output
240v AC
50Hz input
Briton 996 units
NC
+
+
-
++
---
P.R. relay controlled by alarm
Unit is polarised indicated by the
red (+VE) and black (-VE) wires.
Transformer
rectifier unit
(F.S.R.)
0996/091/00
Issue 01

Ver el manual de Briton 996 aquí, gratis. Este manual pertenece a la categoría No categorizado y ha sido calificado por 1 personas con un promedio de 7.5 . Este manual está disponible en los siguientes idiomas: Inglés . ¿Tienes alguna pregunta sobre Briton 996 o necesitas ayuda? Haz tu pregunta aquí

¿Necesitas ayuda?

¿Tiene alguna consulta sobre el Briton y la respuesta no está en el manual? Haga su consulta aquí. Proporcione una descripción clara y completa de su problema y su consulta. Cuanto mejor describa su problema y consulta, más fácil será para otros propietarios de Briton proporcionarle una buena respuesta.

Número de preguntas: 0

General
Briton
996
No categorizado
Inglés
Manual de usuario (PDF)

¿No puede encontrar la respuesta a su consulta en el manual? Puede encontrar la respuesta a su consulta en las preguntas frecuentes sobre el Briton 996 más abajo.

¿No aparece tu pregunta? Haz tu pregunta aquí

No hay resultados